Experimental Research on Second Generator in Pump2Free Lithium Bromide Absorption Chiller System [J]. 2006, 40(1): 62-0066. DOI: 10.7652/xjtuxb200601015.
Experimental Research on Second Generator in Pump2Free Lithium Bromide Absorption Chiller System [J]. 2006, 40(1): 62-0066. DOI: 10.7652/xjtuxb200601015.DOI:
A second generator is designed in a new solar p ump2f ree lit hium bromide absorption<br />chiller system to improve t he solar energy utility efficiency by decreasing t he temperat ure of heat<br />source (minimum starting temperat ure 68 -
wide operation temperat ure ranging f rom 80 - to<br />93 -)
based on the falling film absorber
t he falling film evaporator
t he lunate thermosip hon<br />elevation t ube and condenser
etc. The second generator facilitates establishing pressure differ2<br />ence between evaporator and condenser
and enhancing t he performance of absorber to make t he<br />differential concent ration and absorptivity increase in a lower initial solution concent ration. By<br />t he aid of second generator
t he yield of condensate increases 1168 times
the evaporation effect is<br />heightened obviously. The temperat ure difference of cooling water in absorber and the tempera2<br />t ure difference of chilled water in evaporator increase