针对传统的距离保护应用于交直流混联系统
特别是当直流系统发生换相失败时存在暂态超越的问题
分析发现交直流混联系统直流侧发生换相失败时
故障暂态信号中含有大量衰减缓慢的低频分量、非周期分量及高频分量
这是引起距离保护暂态超越的根本原因.同时
给出一种先利用分布参数模型将保护安装处的电压、电流补偿至整定点
再采用R-L线路模型建立微分方程
识别出整定点与故障点之间距离的保护方案.动模数据仿真结果表明
该方案在特高压、长线路末端故障时能够有效地防止暂态超越
不受线路分布电容、低频分量以及非周期分量的影响
提高了长线距离保护的动作可靠性.
The traditional distance protections applied to the AC-DC power system usually induce transient overreach
especially for the Inverter commutation failure in DC system. It is found that the transient overreach in AC-DC power system is due to fault transient signals containing a large number of low-frequency components of the slow decay and non-periodic components and high frequency components. The voltage and current of tuning point based on distributed-parameter model are calculated
and the equations for identifying the distance between tuning point and the point of failure by R-L model are established to put forward a protection scheme. The simulations show the ability for distinguish internal fault from external fault and preventing transient overreach.
陈建国,宋璇坤.阻抗继电器的超越与对策[J].继电器,1991,19(2):7-13.
CHEN Jianguo, SONG Xuankun. The overreach of distance relay and solution[J]. Relay, 1991,19(2):7-13.
索南加乐,许庆强,宋国兵,等.自适应接地距离继电器[J].电力系统自动化,2005,29(17):54-58.
SUONAN Jiale, XU Qingqiang, SONG Guobing, et al. Adaptive earth fault distance relay[J]. Automation of Electric Power Systems, 2005, 29(17):54-58.
苏文辉,李刚.一种能滤除衰减直流分量的改进全波傅里叶算法[J].电力系统自动化,2002,26(23):42-44.
SU Wenhui, LI Gang. An improved full-wave Fourier algorithm for filtrating decaying DC component[J]. Automation of Electric Power Systems, 2002, 26(23): 42-44.
熊刚,陈陈.一种能滤除衰减直流分量的交流采样新算法[J].电力系统自动化,1997,21(2):24-26.
XIONG Gang, CHEN Chen. A novel alternating current sampling algorithm for filtering decaying direct current component[J]. Automation of Electric Power Systems, 1997, 21(2): 24-26.
陈朝晖,黄少锋,陶慧良,等. 一种新的基于转矩大小的距离保护Ⅰ段反时限特性实现方法[J]. 电力系统自动化,2003,27(20):54-61.
CHEN Zhaohui, HUANG Shaofeng, TAO Huiliang, et al. A new implementation method of the zoneⅠrelay of the distance protection with inverse time characteristics based on the magnitude of the torque[J]. Automation of Electric Power Systems, 2003, 27(20): 54-61.
索南加乐,刘文涛,张健康,等. 基于波形系数的自适应距离保护[J]. 电力系统自动化, 2005,29(5):38-44.
SUONAN Jiale, LIU Wentao, ZHANG Jiankang, et al. Adaptive distance protection based on waveform factor[J]. Automation of Electric Power Systems, 2005, 29(5): 38-44.
索南加乐,顾嘉,薛晓辉,等. 基于工频量补偿算法的长线距离保护[J]. 电力系统自动化, 2007,31(23):57-60.
SUONAN Jiale, GU Jia, XUE Xiaohui, et al. Distance protection based on frequency-domain compensation algorithm[J]. Automation of Electric Power Systems, 2007, 31(23): 57-60.
宋国兵,索南加乐,许庆强.基于双回线环流的时域法故障定位[J].中国电机工程学报,2004,24(3):24-29.
SONG Guobing, SUONAN Jiale, XU Qingqiang. A novel time-domain algorithm for locating faults on parallel transmission lines by circulating circuit[J]. Proceedings of the CSEE, 2004, 24(3):24-29.