It is important for accomplishing online monitoring and risk prediction of flashover from contaminated insulators to develop efficient algorithm for identifying surface charge state of insulators.Following the analysis of surface discharge character
a novel discernment algorithm is proposed
where the discernment process contains three steps: the discharge states are discerned based on leakage current via Bayes discernment algorithm; the stages are discerned based on humidity through fuzzy theory; the results from the first and two steps are combined by an arbitration operation and the final result about the discharge state is achieved. The validity testing results show that the novel algorithm is endowed with a good universality and the algorithm trained out by one group data enables to identify the discharge state of the other artificial test with good accuracy and the mistake happens within the adjacent states. So the algorithm is suitable for discerning surface discharge state of HV insulators through LC and humidity signal.
关键词
Keywords
references
贺博,林辉.绝缘子污秽闪络的研究现状及思索[J].电瓷避雷器,2006,44(2):7-11.
HE Bo, LIN Hui. Present status and future prospects for flashover research of contaminated insulators [J]. Insulator And Surge Arresters, 2006, 44(2): 7-11.
LI Zhi, WANG Yongjiang, WANG Liming et al. Research of leakage current and discharge phenomena of Insulators [J]. High Voltage Engineering, 2002,28(120): 1-4.
AMARH F. Electric transmission line flashover prediction system[D].Tempe, USA:Arizona State University, 2001:30-100.