西安交通大学叶轮机械研究所,西安,710049
网络首发:2011-05-10,
纸质出版:2011
移动端阅览
何纬峰, 戴义平. 环境风速对空冷凝汽器运行性能的影响[J]. 西安交通大学学报, 2011,45(5):31-35.
Effect of Wind Speed on Performance of an Air-Cooled Steam Condenser[J]. 2011, 45(5): 31-35.
通过建立2×600 MW直接空冷电厂的数值模型
采用Fluent软件计算得到了环境风速影响下空冷凝汽器风机的运行规律
并通过加载翅片管换热器内部汽轮机排汽的凝结程序
分析了环境风速对空冷凝汽器换热量的影响机理.计算结果表明:在环境风速的扰动作用下
环境风速由0 m/s上升至12 m/s时空冷凝汽器周围的流场变化使凝汽器总容积效率下降了15.9%
迎风面风机的容积效率下降幅度更是高达43.6%
而空冷凝汽器的换热量也相应地从1 695.2 MW下降至1 418.6 MW.通过分析获得了环境风速对空冷凝汽器运行性能的影响机理
可为空冷电厂运行背压的预测提供参考.
A numerical model for a 2×600 MW air-cooled power plant was established and the commercial code
FLUENT
was applied to obtain the operation patterns of the air-cooled fans at different wind speeds. The influence of the wind speed on the heat transfer rate was also analyzed using the program for condensation of the exhaust steam in the finned tube exchangers. The result shows that the total volume effectiveness of the air-cooled condenser decreases by 15.9% due to the difference of the flow field around the condenser and the volume effectiveness of the windward fans decreases by up to 43.6% when the wind speed increases from 0 m/s to 12 m/s
leading to the decrease in the heat transfer rate of the heat exchangers from 1 695 MW to 1 418.6 MW.
赵文升,王松岭,高月芬,等.直接空冷系统中热风回流现象的数值模拟和分析[J].动力工程, 2007,27(4):487-492.
ZHAO Wensheng, WANG Songling, GAO Yuefeng, et al. Numerical simulation and analysis of the hot air recirculation phenomenon observed in the direct air-cooling systems[J]. Journal of Power Engineering, 2007,27(4):487-492.
段会申,刘沛清,赵万里.电厂直接空冷系统热风回流的数值模拟 [J].动力工程, 2008,28(3):395-399.
DUAN Huishen, LIU Peiqing, ZHAO Wanli.Numerical simulation on hot wind recirculation for direct air-cooled system[J].Journal of Power Engineering, 2008,28(3):395-399.
周兰欣,白中华,李卫华,等.自然风对空冷凝汽器换热效率影响的数值模拟 [J].动力工程, 2008,28(1):104-107.
ZHOU Lanxin, BAI Zhonghua, LI Weihua,et al. Numerical simulation for the effects of natural wind on heat exchanger efficiency of air-cooled condenser[J]. Journal of Power Engineering, 2008,28(1):104-107.
何纬峰, 戴义平, 马庆中,等.环境风影响下直接空冷单元背压预测研究 [J].西安交通大学学报, 2011,45(1): 15-20.
HE Weifeng, DAI Yiping, MA Qingzhong, et al. Prediction of back pressure on the air-cooled unit with effect of ambient wind [J]. Journal of Xi'an Jiaotong University, 2011,45(1):15-20.
van ROOYEN J A, KROGER D G. Performance trends of an air-cooled steam condenser under windy conditions [J/OL]. ASME Journal of Engineering for Gas Turbines and Power, 2008, 130(2)[2010-07-01]. http:∥dx.doi.org/10.115/1.2771567.
何纬峰.环境风速对直接空冷电厂运行性能影响的研究 [D].西安:西安交通大学, 2009.
张文元.环境风场对直接空冷发电系统的影响[J].华北电力技术, 2006(S1):4-8.
ZHANG Wenyuan.Influence of wind environment on direct air cooling generating unit [J].North China Electric Power, 2006(S1):4-8.
0
浏览量
4
下载量
2
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621