Comparison of Energy Consumption of Air Cooling and Air-Liquid Hybrid Cooling in Data Centers
To address the energy consumption differences between new and traditional cooling methods in data centers
this study establishes an energy utilization model for data centers
provides a detailed overview of the key components of servers and cooling systems
as well as one-dimensional and threedimensional coupling modeling methods
performs an in-depth energy consumption analysis of air cooling and air-liquid hybrid cooling system components. Air cooling represents the traditional cooling method
while air-liquid hybrid cooling is a new cooling approach aimed at high-power servers. Under the condition that the dimensions of the server components
chip power
and maximum chip temperature are the same
a comparative analysis of the results from the two cooling methods is conducted to quantify the differences in energy consumption. The calculation results indicate that
compared to traditional air cooling
hybrid cooling reduces total energy consumption by 16.19%;hybrid cooling mainly lowers the energy consumption of chiller compressors and server fans. Additionally
due to the absence of an air-water heat exchanger in the liquid cooling system in the case of the hybrid cooling method
the system is simplified and can further enhance the heat transfer efficiency of both the primary and secondary cooling sides of the data center. The air-liquid hybrid cooling method demonstrates a significant advantage in reducing energy consumption.
关键词
Keywords
references
MOAZAMIGOODARZI H , GUPTA R , PAL S , et al . Modeling temperature distribution and power consumption in IT server enclosures with row-based cooling architectures [J ] . Applied Energy , 2020 , 261 : 114355 .
RAMAKRISHNAN B , ALISSA H , MANOUSAKIS I , et al . CPU overclocking:a performance assessment of air,cold plates,and two-phase immersion cooling [J ] . IEEE Transactions on Components,Packaging and Manufacturing Technology , 2021 , 11 ( 10 ): 1703 - 1715 .
HUANG Jianwen , CHEN Cheng , GUO Guiyang , et al . A calculation model for typical data center cooling system [C ] // Journal of Physics:Conference Series . Bristol, United Kingdom : IOP Publishing , 2019 : 012022 .
CHO J , PARK B , JANG S . Development of an independent modular air containment system for high-density data centers:experimental investigation of rowbased cooling performance andPUE [J ] . Energy , 2022 , 258 : 124787 .
CHI Y Q , SUMMERS J , HOPTON P , et al . Case study of a data centre using enclosed,immersed,direct liquid-cooled servers [C ] // 2014 Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM) . Piscataway,NJ,USA : IEEE , 2014 : 164 - 173 .
NADJAHI C , LOUAHLIA H , LEMASSON S . Areview of thermal management and innovative cooling strategies for data center [J ] . Sustainable Computing:Informatics and Systems , 2018 , 19 : 14 - 28 .
WATSON B , VENKITESWARAN V K . Universal cooling of data centres:a CFD analysis [J ] . Energy Procedia , 2017 , 142 : 2711 - 2720 .
YATSKOV A . Comparison of HPC/telecom data center cooling methods by operating and capital expense, electronics cooling [EB/OL ] .[ 2025-05-01 ] . https://www.electronicscooling.com/2015-/05/comparison-ofhpctelecom-data-center-cooling-methods-by-operatingand-capital-expense/ .
ALKRUSH A A , SALEM M S , ABDELREHIM O , et al . Data centers cooling:a critical review of techniques,challenges,and energy saving solutions [J ] . International Journal of Refrigeration , 2024 , 160 : 246 - 262 .
CHOWDHURY U , SIDDARTH A , SAHINI M , et al . Raising inlet air temperature for a hybrid-cooled server retrofitted with liquid cooled cold plates [C ] // ASME 2018 International Mechanical Engineering Congress and Exposition . New York,USA : ASME , 2018 : V08BT10A044 .
FAN Yuehong , SUN Yanbing , ZHANG Guocheng , et al . Cold plate liquid cooling solution for hot-swapped components in server system [C ] // 202423rd IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm) . Piscataway,NJ,USA : IEEE , 2024 : 1 - 4 .
HEYDARI A , RADMARD V , ESLAMI B , et al . Liquid to air cooling for high heat density liquid cooled data centers [C ] // ASME 2022 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems . New York,USA : ASME , 2022 : V001T01 A005 .
LIU Shengchun , XU Zhiming , LI Xueqiang , et al . Simulation study on key parameters of single-phase liquid-cooling cabinet in data centers [J ] . Journal of Refrigeration , 2023 , 44 ( 2 ): 159 - 166 .
TANG Yuqing , WANG Zhanjun , HU Xiaojun , et al . Multiscale modeling of single-phase immersion cooling for data center [J/OL ] . Journal of Xi’an Jiaotong University .( 2025-04-08 )[ 2025-04-25 ] . http://kns.cnki.net/kcms/detail/61.1069.t.20250407.1118.004.html .
HUANG Guorui , LIU Hongwei , ZHAO Yao , et al . Energy consumption analysis of data center cooling system based onTRNSYS [J ] . Chinese Journal of Refrigeration Technology , 2024 , 44 ( 3 ): 36 - 43 .
CHO J , KIM Y . Improving energy efficiency of dedicated cooling system and its contribution towards meeting an energy-optimized data center [J ] . Applied Energy , 2016 , 165 : 967 - 982 .
HAM S W , KIM M H , CHOI B N , et al . Energy saving potential of various air-side economizers in a modular data center [J ] . Applied Energy , 2015 , 138 : 258 - 275 .
LOU Xiaojun , WANG Xuejun . Energy efficiency of water-cooled chilled water system in data center [J ] . Building Energy Efficiency , 2018 , 46 ( 1 ): 19 - 22 .
CHENG Bo , CHEN Yi , WANG Dongliang , et al . Research and application of energy saving operation mode of water cooling system in data center [J ] . Digital Communication World , 2023 ( 2 ): 146 - 148 .
陶文铨 . 数值传热学 [M ] . 2版 . 西安 : 西安交通大学出版社 , 2013 .
Mechatronics Corporation . AC,DC and EC fans and blowers from mechatronics inc .[EB/OL ] .[ 2025-05-01 ] . https://www.mechatronics.com/ .
WANG Zixing , HE Pu , LI Nan , et al . A fuel cell powered rack prototype for data center application with waste heat recovery:design consideration and experimental verification [J ] . Energy Conversion and Management , 2024 , 318 : 118892 .
Comparison of energy consumption of air cooling and air-liquid hybrid cooling in data centers
Active Distribution Network Congestion Management Considering Flexible Migration Characteristics of Data Center Workload
Multiscale Modeling of Single-Phase Immersion Cooling in Data Centers
Research on the Design and Operation Optimization of Distributed Multi-Energy Systems for Data Centers
Windage Loss and Flow Characteristics in Impeller Back Gaps of sCO2 Radial Inflow Turbines
Related Author
LI Yuting
LI Zhiyang
ZHANG Runjie
TAO Wenquan
TIAN Zihao
HOU Guo
GU Chenjia
WANG Jianxue
Related Institution
Xi'an key laboratory of energy-saving and low-carbon technology of data centers, key laboratory of thermo-fluid science and engineering, ministry of education, school of energy & power engineering, Xi’an Jiaotong University
Xi'an key laboratory of energy-saving and low-carbon technology of data centers, key laboratory of thermo-fluid science and engineering, ministry of education, school of energy & power engineering, Xi’an Jiaotong University
School of Electrical Engineering, Xi'an Jiaotong University
State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University
School of Electrical and Information Engineering, Tianjin University