Lightning Direct Effect of Optical Fiber Overhead Ground Wires under Continuous Two Lightning Components[J]. 2018, 52(2): 82-88.
DOI:
Lightning Direct Effect of Optical Fiber Overhead Ground Wires under Continuous Two Lightning Components[J]. 2018, 52(2): 82-88.DOI: 10.7652/xjtuxb201802013.
Lightning Direct Effect of Optical Fiber Overhead Ground Wires under Continuous Two Lightning Components
By analyzing the current standard of lightning testing and performance for the optical ground wire(OPGW)
the lightning direct effect testing system with an adjustable discharge gap for the OPGW is constructed. The lightning strike characteristics and damage performance of OPGW under different experimental conditions of variable DC currents and discharge gaps are evaluated in the experiments. The mechanism of lightning direct effect and conducting performance of OPGW are explored preliminarily. It is found that as the Al-Steel outer layer of the OPGW
the erosion degree of the aluminum-clad steel wire increases with the increasing transfer charge of DC current C component. When the transfer charge gets about 200 C
the temperature of the OPGW surface after the lightning strikes is estimated for more than 3 700 ℃
and more than 30% of the strands are damaged severely. Moreover
when the length of discharge gap increases from 5 cm to 6 cm
the temperature rise of OPGW due to the lightning strike decreases and the lightning damage degree is reduced over 40%.
关键词
Keywords
references
梁芝贤, 穆国强. OPGW的应用 [J]. 光通信技术, 2007, 31(1): 62-64.
LIANG Zhixian, MU Guoqiang. The using of OPGW [J]. Optical Communication Technology, 2007, 31(1): 62-64.
XU Yongjun, ZHOU Jianhua, ZHAO Houpeng, et al. Development and application of ultra-high strength optical fiber composite overhead ground wire(OPGW)[J]. Electric Power Information and Communication Technology, 2016(11): 62-67.
CHISHOLM W A, LEVINE J P, CHOWDHURI P. Lightning arc damage to optical fiber ground wires(OPGW): parameters and test methods [C]∥IEEE Power Engineering Society Summer Meeting. Piscataway, NJ, USA: IEEE, 2001: 88-93.
YOKOYA M, KATSURAGI Y, GODA Y, et al. Development of lightning-resistant overhead ground wire [J]. IEEE Transactions on Power Delivery, 1994, 9(3): 1517-1523.
IEC. Optical fiber cable part 4-1: aerial optical cable for high-voltage power line: IEC 60794-4-1-1999 [S]. Geneva, Switzerland: IEC, 1999.
SAE. Aircraft lightning environment and related test waveforms: ARP 5412A [S]. Warrendale, PA, USA: SAE, 2005.
LIU Yakun, DAI Mingqiu, XIAO Yao, et al. Influence factors of metal materials struck by simulated lightning currents [J]. High Voltage Engineering, 2017, 43(5): 1445-1452.
LU L, LIANG Y, LI B, et al. Experimental study on location of lightning stroke on OPGW by means of a distributed optical fiber temperature sensor [J]. Optics Laser Technology, 2015, 65(9): 79-82.
IWATA M, OHTAKA T, KUZUMA Y, et al. Development of a method of calculating the melting characteristics of OPGW strands due to DC arc simulating lightning strike [J]. IEEE Transactions on Power Delivery, 2013, 28(3): 1314-1321.
IWATA M, OHTAKA T, GODA Y. Melting and breaking of 80 mm2 OPGWs by DC arc discharge simulating lightning strike [C]∥International Conference on Lightning Protection. Piscataway, NJ, USA: IEEE, 2016: 1-4.
DUBITSKY S D, KOROVKIN N V, HAYAKAWA M, et al. Thermal resistance of optical ground wire to direct lightning strike [C]∥URSI International Symposium on Electromagnetic Theory. Piscataway, NJ, USA: IEEE, 2013: 108-111.
IEC. Optical fiber cable part 4-1: sectional specification: aerial optical cable along electrical power line: IEC 60794-4-2003 [S]. Geneva, Switzerland: IEC, 2003.
IEEE. IEEE standard for testing and performance for optical ground wire(OPGW)for use on electrical utility power lines: IEEE STD 1138-2009 [S]. Piscataway, NJ, USA: IEEE, 2009.
CHEMARTIN L, LALANDE P, PEYROU B, et al. Direct effects of lightning on aircraft structure: analysis of the thermal, electrical and mechanical constraints [J]. Aerospace Lab, 2012, AL-09(5): 1-15.
OGASAWARA T, HIRANO Y, YOSHIMURA A. Coupled thermal-electrical analysis for carbon fiber/epoxy composites exposed to simulated lightning current [J]. Composites: Part A Applied Science Manufacturing, 2010, 57(8): 973-981.
HE J, GU S, ZENG R, et al. Propagation models for motion processes of long ac arcs on overhead lines [J]. Electric Power Systems Research, 2011, 81(12): 2066-2073.