PI Parameter Setting of Compressor Refrigerating Capacity Test Systems Adopting the Unified Modeling Language[J]. 2016, 50(8): 137-142.
DOI:
PI Parameter Setting of Compressor Refrigerating Capacity Test Systems Adopting the Unified Modeling Language[J]. 2016, 50(8): 137-142.DOI: 10.7652/xjtuxb201608022.
PI Parameter Setting of Compressor Refrigerating Capacity Test Systems Adopting the Unified Modeling Language
Mathematical models based on the Modelica language are built to solve the problem that the compressor test system is a dynamic system with the characteristics of great inertia
pure time-delay
strong coupling and multiple disturbances
and cannot rapidly reach a stable state. The Ziegler-Nichols method is applied to the simulation software Dymola to obtain initial PI parameters. The step excitation is given in the expansion valve under the condition that the parameters of other elements are fixed to constants
and then the PI controller is added after removing the step excitation. The influences of PI parameters on the discharge pressure
the suction superheat
the suction pressure and the subcooled temperature are concluded. It is found that increasing the proportional gain or decreasing the integrating gain could be used to solve the overshoot problems of the discharge pressure and the suction superheat
and that decreasing the integrating gain is also beneficial to the shock condition. When the suction pressure is overshoot
the proportional gain should be decreased. If the response time is too long
the proportional gain should be increased or the integrating gain should be decreased. Moreover
the subcooled suction could be improved by decreasing both the proportional gain and the integrating gain. These results could be considered as a reference for the practical engineering.
SHEN Xi, HUANG Yuejin, BAO Yumei, et al. Research of control tactics for operating conditions in compressor refrigerating capacity test system [J]. Compressor Technology, 2004, 12(5): 4-6.
Underwood C P. HVAC control systems: modelling, analysis and design [M]. New York, USA: E FN Spon, 1999: 250-251.
AN Dawei, WANG Jiangjiang, LOU Chengzhi. Application of neural network PID controller to the constant temperature air conditioning system in tall and big space [J]. Journal of Tianjin University, 2005, 38(3): 268-273.
WANG Fenghao, MENG Xiangzhao, YU Bingfeng. Simulation study on the control of variable frequency air conditioning systems [J]. Fluid Machinery, 1998, 26(3): 45-47.
ZHENG Zonghe, LIANG Jiang, NIU Baolian, et al. Simulation study on neural PID control of variable frequency air conditioning systems [J]. Heating Ventilating and Air Conditioning, 2004, 34(12): 93-95.
白建波, 张小松. 一种具有鲁棒性能的PI控制器在空调系统中的研究 [J]. 建筑热能通风空调, 2007, 26(1): 1-6.BAI Jianbo, ZHANG Xiaosong. Research on PI controllers with robustness in air-conditioning systems [J]. Building Energy Environment, 2007, 26(1): 1-6.
LI Xuquan, CHEN Jiangping, CHEN Zhijiu. A new method for controlling refrigerant flow in automobile air conditioning [J]. Applied Thermal Engineering, 2004, 24(7): 1073-1085.
MA Shanwei, ZHANG Chuan, CHEN Jiangping. Experimental research on refrigerant mass flow coeffieient of electronic expansion valve [J]. Applied Thermal Engineering, 2005, 25(14/15): 2351-2366.