To analyze the permanent magnet synchronous generator(PMSG)fault characteristics
a simplified model of grid-side converter and external characteristics model of controller with chopper are proposed. Grid-side converter is an electric energy balance system under controlling action
its complex structure is ignored and the function and external characteristics are retained only. To reveal the PMSG short-circuit current is to analyze the three-phase current response under the action of turbine terminal voltage sag. A comparison with detailed model indicates that when chopper circuit does not operate
the value of PMSG current is determined by its output power and the degree of voltage sag; besides 50 Hz component
there are components whose frequencies are related to the control parameters; the fault current firstly increases gradually and then decreases to a steady value; with the increasing voltage sag degree
the maximum fault current gets greater and the corresponding period and transient decay time become longer; when chopper circuit operates
the fault current is just the maximum converter current.
ZHANG Liying, YE Tinglu, XIN Yaozhong, et al. Problems and measures of power grid accommodating large scale wind power [J]. Proceedings of the CSEE, 2010, 30(25): 1-9.
CHI Yongning, LIU Yanhua, WANG Weisheng, et al. Study on impact of wind power integration on power system [J]. Power System Technology, 2007, 31(3): 77-81.
WANG Chenqing, SONG Guobing, LIU Kai, et al. Adaptability analysis of fault component protection of power systems with wind farms [J]. Proceedings of the CSEE, 2014, 34(31): 5485-5492.[5] 栗然, 高起山, 刘伟. 直驱永磁同步风电机组的三相短路故障特性 [J]. 电网技术, 2011, 35(10), 153-158.
LI Ran, GAO Qishan, LIU Wei. Characteristics of direct-driven permanent magnet synchronous wind power generator under symmetrical three-phase short-circuit fault [J]. Power System Technology, 2011, 35(10): 153-158.
ZHANG Baohui, WANG Jin, LI Guanghui, et al. Analysis on fault features of wind turbine generators concentratedly connected to power grid [J]. Power System Technology, 2012, 36(7): 176-183.
HU Shuju, LI Jianlin, XU Honghua. Analysis on the low voltage ride through capability of direct drive permanent magnetic generator wind turbines [J]. Automation of Electric Power Systems, 2007, 31(17): 73-77.
HU Shuju, LI Jianlin, XU Honghua. Modeling on converters of direct driven wind power system and its performance during voltage sags [J]. High Voltage Engineering, 2008, 34(5): 949-954.
ABEDINI A, NASIRI A. PMSG wind turbine performance analysis during short circuit faults [C]∥Electrical Power Conference 2007. Piscataway, NJ, USA: IEEE, 2007: 160-165.