Experimental Research on V-A Characteristics of Metal Oxide Varistors under Very Fast Transient Wave
Very fast transient overvoltage(VFTO)waveform generator is designed and constructed based on the second-order circuit theory
and the voltage and current measurement scheme is determined. Two different specifications of representative metal oxide varistors(MOV)are chosen as the samples
and the V-A characteristic and impedance behavior of MOV under impulse current within the range of 80-150 ns are investigated. The experiments indicate that as the current peak remains constant
the residual voltage under VFTO reaches approximately 9%-16% higher than the standard lightning impulse voltage; with the rising applied current from 80 ns to 150 ns
the voltage peak value increases by 10% to 20%; the voltage peak comes obviously earlier than the current peak
ZOU Jianhua, KANG Ning, LI Cheng, et al. Research on mechanism in formation and depression of very fast transient overvoltage[J]. Journal of Xi'an Jiaotong University, 2005, 39(4): 417-420.
DAI Min, GU Dingxie, SUN Gang, et al. Study on full-scale 1000 kV gas insulated switchgear test circuit for very fast transient overvoltage[J]. Proceedings of the CSEE, 2011, 31(31): 28-36.
LI Liuling, HU Panfeng, QIU Yuchang, et al. Suppression of transient ground potential rise in gas insulated substation[J]. Journal of Xi'an Jiaotong University, 2005, 39(6): 624-627.
ZHANG Wenyuan, SHI Baozhuang, QIU Yuchang. Research on the measurement of very fast transient overvoltage by differentiating/integrating system[J]. Journal of Xi'an Jiaotong University, 1996, 30(11): 74-79.
LI Liuling, HU Panfeng, QIU Yuchang, et al. Analysis of very fast transient overvoltage calculation affected by different transformer winding models[J]. Journal of Xi'an Jiaotong University, 2005, 39(10): 1160-1164.
CHEN Yuyuan, YUAN Meizhen. Research on measurement techniques for fast transient overvoltage[J]. Journal of Xi'an Jiaotong University, 1992, 26(5): 81-87.
SHI Baozhuang, ZHANG Wenyuan, QIU Yuchang. Research on differentiating-integrating system for the measurement of very fast transient overvoltage in GIS[J]. Journal of Xi'an Jiaotong University, 1997, 31(11): 72-75.
SHU Yinbiao, CHEN Weijiang, LI Zhibing, et al. Experimental research on very-fast transient overvoltage in 1100 kV gas-insulated switchgear[J]. IEEE Transactions on Power Delivery, 2013, 28(1): 458-466.
SCHMIDT W. Behavior of MO-surge-arrester blocks to fast transients[J]. IEEE Transactions on Power Delivery, 1989, 4(1): 292-300.
VALSALAL P, USA S, UDAYAKUMAR K. Response of metal oxide arrester in gas-insulated substation and methods to improve its dynamic characteristics[J]. IET Science, Measurement and Technology, 2012, 6(4): 222-228.
VALSALAL P, USA S, UDAYAKUMAR K. Modelling of metal oxide arrester for very fast transients[J]. IET Science, Measurement and Technology, 2011, 5(4): 140-146
VALSALAL P, USA S, UDAYAKUMAR K. Importance of capacitance on metal oxide arrester block model for VFTO applications[J]. IEEE Transactions on Power Delivery, 2011, 26(2): 1294-1295.
LI Zhibing, WANG Hao, YAN Xianglian, et al. Analysis of test and model for metal oxide arrester under steep-front wave[J]. High Voltage Engineering, 2012, 38(10): 2698-2706.
IEC. IEC60099-4: 2006 Surge arresters: part 4 Metal-oxide surge arresters without gaps for a. c. systems[S]. Geneva, Switzerland: IEC, 2006.
KING I, FUNABASHI T, SASAKI H, et al. Study of ZnO arrester model for steep front wave[J]. IEEE Transactions on Power Delivery, 1996, 11(2): 834-839.
IEEE Working Group 3.4.11. Modeling of metal oxide surge arresters[J]. IEEE Transactions on Power Delivery, 1995, 10(2): 778-785.
PINCEITI P, GIANNETTONI M. A simplified model for zinc oxide surge arresters[J]. IEEE Transactions on Power Delivery, 1999, 14(2): 393-398.
LI Hongjie, BIRLASEKARAN S, CHOI S S. A parameter identification technique for metal-oxide surge arrester models[J]. IEEE Transactions on Power Delivery, 2002, 17(3): 736-741.