Experimental Investigation for Effects of Electronic Expansion Valve Opening on Exergy Loss in Transcritical CO2 System[J]. 2014, 48(3): 12-16. DOI: 10.7652/xjtuxb201403003.
DOI:
Experimental Investigation for Effects of Electronic Expansion Valve Opening on Exergy Loss in Transcritical CO2 System[J]. 2014, 48(3): 12-16. DOI: 10.7652/xjtuxb201403003.DOI:
Experimental Investigation for Effects of Electronic Expansion Valve Opening on Exergy Loss in Transcritical CO2 System
the effects of electronic expansion valve(EEV)opening on the exergy loss of different components in the transcritical CO
2
system were investigated. The experimental table for the transcritical CO
2
system with an EEV was constructed
and the operation parameters of the CO
2
system were measured under constant water inlet temperature and different EEV opening. Based on the experimental data
the effects of the EEV opening on the COP
the total exergetic efficiency of system and relative exergy loss of all components were analyzed. The exergetic
efficiency for the different components was also presented at the optimal EEV opening
and with the gas cooler side water inlet temperature of 30 ℃ and the evaporator side water inlet temperature of 15 ℃. According to relative exergy loss and exergetic efficiency for all components at the optimal EEV opening
the improvement room of the components was analyzed. The results show that the compressor and the gas cooler account for 49.4% and 18.9% of the total exergy loss respectively
and the exergetic efficiencies of these two components are 60.7% and 37.6% respectively. Thus compressor and gas cooler are endowed with abundant improving potential.
关键词
Keywords
references
LORENTZEN G, PETTERSEN J. A new efficient and environmentally benign system for car air-conditioning[J]. Int J Refrig, 1993, 16(1): 4-12.
ROBINSON D M, GROLL E A. Efficiencies of transcritical CO2 cycles with and without an expansion turbine: Rendement de cycles transcritiques au CO2 avec et sans turbine d'expansion[J]. Int J Refrig, 1998, 21(7): 577-589.
FARTAJ A, TING D S K, YANG W W. Second law analysis of the transcritical CO2 refrigeration cycle[J]. Energ Convers Manage, 2004, 45(13/14): 2269-2281.
YANG J L, MA Y T, MIN X L, et al. Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander[J]. Energy, 2005, 30(7): 1162-1175.
SARKAR J, BHATTACHARYYA S, GOPAL M R. Transcritical CO2 heat pump systems: exergy analysis including heat transfer and fluid flow effects[J]. Energ Convers Manage, 2005, 46(13/14): 2053-2067.
TAO Y B, HE Y L, TAO W Q. Exergetic analysis of transcritical CO2 residential air-conditioning system based on experimental data[J]. Appl Energ, 2010, 87(10): 3065-3072.
BAEK C, HEO J, JUNG J, et al. Optimal control of the gas-cooler pressure of a CO2 heat pump using EEV opening and outdoor fan speed in the cooling mode[J]. Int J Refrig, 2013, 36(4): 1276-1284.