To investigate the mechanism of partial discharge(PD)of insulation defects in gas-insulated metal-enclosed switchgear(GIS)under impulse voltage
time-frequency characteristics of optical signals and current signals of PD are analyzed with short time Fourier transform(STFT)
pseudo Wigner-Ville distribution theory and Gabor distribution theory. The analysis reveals that: 1)The time-frequency characteristics of PD signals can be effectively extracted; 2)Gabor distribution of PD signals is endowed with the best time-frequency aggregation behavior without cross-interference items and reflects the most detailed characteristics of PD signals in time-frequency plane; 3)STFT of PD signals possesses the poorest time-frequency aggregation behavior and 4)Pseudo Wigner-Ville distribution of PD signals includes several inherent cross-interference terms. The time-frequency characteristics of the optical signals and the current signals of PD are different and the rising time of the optical pulse is less than that of the current pulse in time-frequency plane.
SARATHI R, KRISHNAMURTHI M, REJI P. Breakdown characteristics of a short air gap with conducting particle under composite voltages [C]∥Conference on Electrical Insulation and Dielectric Phenomena. Minneapolis,MN,USA:IEEE, 1997:19-22.
CIGRE Joint Working Group 33/23.12. Insulation coordination of GIS: return of experience,on site tests and diagnostic techniques [C]∥International Council on Large Electric Systems. Paris,France:[s.n.], 1998:67-97.
XU Shishan, MENG Kefeng, LIU Wenquan. Analysis of 363 kV gas insulated switchgear charging flash over fault [J]. High Voltage Engineering, 2007,43(1):74-76.
SUN Qiang, DONG Ming, REN Zhong. Field test and analysis of partial discharge on GIS under impulse voltage [J]. High Voltage Engineering, 2012,38(3):639-644.
LIANG Guishu, ZHOU Hongwei, DONG Huaying. Joint time-frequency analysis on PD pulse signals in GIS [C]∥Asia-Pacific Conference on Environmental Electromagnetics. Piscataway, NJ, USA: IEEE, 2003:194-197.
WANG Meng, TAN Kexiong, GAO Wensheng, et al. Time-frequency distribution method for extracting features of partial discharge pulse shape [J]. Transactions of China Electrotechnical Society, 2002,17(2):76-79.
吴正国,夏立,尹为民. 现代信号处理技术 [M]. 武汉:武汉大学出版社, 2003:83-85.
ABEYSEKERA S S, BOASHASH B. Methods of signal classification using the images produced by the Wigner-Ville distribution [J]. Pattern Recognition Letters, 1991,12:717-729.
YUAN Peng, SI Wenrong, LI Junhao, et al. Time-frequency characteristics of partial discharge pulse with Wigner-Ville distributions [J]. High Voltage Apparatus, 2008:44(6):524-526.
LIU Weidong, LIU Shanghe, WANG Lei. Time-frequency analysis of partial discharge signal by Gabor transform [J]. High Voltage Engineering, 2007,33(8):40-43.
JANSSEN A J E M. Optimal property of the Gaussian window spectrogram [J]. IEEE Trans on Signal Processing, 1991,39(1):202-204.
IEC. IEC 60060-3 High voltage test techniques: part 3 definitions and requirements for on-site tests[S]. Geneva, Swiss: IEC, 2005.