Calculation of Telecommunication Interference Caused by Yunnan-Guangdong ±800 kV Ultra High Voltage DC Transmission Link
|更新时间:2025-07-09
|
Calculation of Telecommunication Interference Caused by Yunnan-Guangdong ±800 kV Ultra High Voltage DC Transmission Link
Vol. 43, Issue 4, Pages: 106-110+115(2009)
作者机构:
西安交通大学电气工程学院,西安,710049
作者简介:
基金信息:
DOI:
CLC:TM721.1
Online First:10 April 2009,
Published:2009
稿件说明:
移动端阅览
Calculation of Telecommunication Interference Caused by Yunnan-Guangdong ±800 kV Ultra High Voltage DC Transmission Link[J]. 2009, 43(4): 106-110+115.
DOI:
Calculation of Telecommunication Interference Caused by Yunnan-Guangdong ±800 kV Ultra High Voltage DC Transmission Link[J]. 2009, 43(4): 106-110+115.DOI:
Calculation of Telecommunication Interference Caused by Yunnan-Guangdong ±800 kV Ultra High Voltage DC Transmission Link
To calculate the telecommunication interference caused by voltage high DC transmission lines
an accurate method is proposed
where the unified fundamental frequency and harmonic load flow algorithm is firstly applied to the telecommunication interference. The distributions of harmonic voltage and harmonic current along DC lines under different operation modes are calculated with an accurate model of converter and the distribution parameters of DC lines
and the influence of the fundamental frequency voltage phase-difference of AC buses at the two terminals is considered. The different parameters and coefficients necessary for telecommunication interference calculation
such as the screening factor of overhead ground wire and coupling impedances
are calculated for Yunnan-Guangdong ±800 kV ultra high voltage DC(UHVDC)transmission lines. The telecommunication interferences caused by positive-sequence and zero-sequence components of harmonic current under different operation modes are estimated respectively. The equivalent interference voltage caused by Yunnan-Guangdong UHVDC transmission lines with different adjacent distances is obtained.
PANG Tingzhi. Standard and calculation of effects of DC transmission lines on the telecommunication lines [J].Power System Technology, 1999, 23(11): 50-54.
IEEE Power Engineering Society. IEEE guide for analysis and definition of DC side harmonic performance of HVDC transmission systems, IEEE Std 1124-2003 [S]. New York, USA: IEEE Power Engineering Society, 2003.
LU Jiayu, JU Yong, PANG Tingzhi. Study on danger and interference effects of ±800 kV DC transmission lines on telecommunication lines [J].Electric Power, 2007, 40(4): 20-24.
ZHOU Changchun, XU Zheng, ZHENG Jin. Calculation of telecommunication interferences caused by Three Gorges-Guangdong HVDC link[J]. Power System Technology, 2003, 27(1): 13-17.
LI Zhanying, LI Jianhua, XIA Daozhi. Analysis of characteristic harmonics in ±800 kV ultra high voltage direct currentpower transmission system [J]. Power System Technology, 2006, 30(24): 6-9.
International Telegram and Telephone Consultative Committee(CCITT). Directives concerning the protection of telecommunication lines against harmful effects from electricity lines [M]. Geneva, Switzerland:CCITT,1989.