In the non-characteristic harmonic load flow algorithm for high voltage direct current(HVDC)system
the nonlinear equations are charactered by the multivariable and huge dimension. Newton-Raphson iterative method is applied to improve the convergence of the non-characteristic harmonic load flow algorithm. The analytic expressions of three phases AC current
DC voltage
and circulation current at Δ side in Y
d transformer are deduced. According to the relationship between the AC-DC network and converter device
balance equations of three-phase harmonic current of AC bus and DC network harmonic current are deduced
the modified equation for whole system is hence constructed and solved iteratively by taking the unified fundamental and characteristic harmonic load flow as the initial value. The non-characteristic harmonic load flows of China Southern Power Grid Yunguang ± 800 kV UHVDC transmission system are evaluated to verify the reasonableness and effectiveness.
SHI Dan, REN Zhen, YU Tao. Overview of harmonic analysis methods in HVDC transmission systems[J]. Electric Power Automation Equipment, 2006, 26(4): 93-97.
XIA Daozhi, SHEN Zanxun. The study of non-characteristic harmonic in DC power transmission system[J]. Journal of Xi'an Jiaotong University, 1985, 18(2): 13-22.
CHEN Hongkun. Analysis of non-characteristic harmonic in AC/DC power transmission system[J]. Journal of Wuhan University of Hydraulic and Electrical Engineering, 1997, 30(4): 51-55.
LI Zhanying, LI Jianhua, XIA Daozhi. Analysis of characteristic harmonics in ±800 kV ultra high voltage direct current power transmission system[J]. Power System Technology, 2006, 30(24):6-9.
SUBBARAO T, REEVE J. Harmonic caused by imbalance transformer impedance and imperfect twelve-pulse operation in HVDC conversion[J]. IEEE Transactions on Power Apparatus and Systems, 1976, 95(5): 1732-1737.