Aiming at the existing analytic methods being lacking in reliable accuracy
a new algorithm for calculating torsional stiffness of bundle overhead transmission lines is presented. Taking the length variation of sub-conductors as a result of torsional deformation of bundle conductors
the actual sub-conductor tension is gained. Then the effects of the sag and a difference of level between the two anchoring points are considered
and a theoretical torsional stiffness formula is deduced in a general bundle conductor span. The parameters affecting the torsional stiffness are revealed by the formula
and the torsional stiffness of bundle conductors can be directly evaluated by means of these parameters. The effectiveness and adaptability for arbitrary span lengths and number of sub-conductors are verified by comparing with the actual measuring results.
关键词
Keywords
references
郭应龙,李国兴,尤传永. 输电线路舞动[M].北京:中国电力出版社,2002:141-144.
NIGOL O, BUCHAN P G. Conductor galloping: part Ⅱ Torsional mechanism[J]. IEEE Transactions on Power Apparatus and Systems,1981,100(2):708-720.
NIGOL O, CLARKE G J, HAVARD D G. Torsional stability of bundle conductors[J]. IEEE Transactions on Power Apparatus and Systems, 1977, 96(5):1666-1674.
WANG Jianwei, LILIEN J. Overhead electrical transmission line galloping: a full multi-span 3-DOF model,some applications and design recommendations[J]. IEEE Transactions on Power Delivery, 1998, 13(3):909-916.
WANG Jianwei, LILIEN J. A new theory for torsional stiffness of multi-span bundle overhead transmission lines[J]. IEEE Transactions on Power Delivery, 1998, 13(4):1405-1411.
KEUTGEN R, LILIEN J,YUKINO T. Transmission line torsional stiffness: confrontation of field-tests line and finite element simulations[J].IEEE Transactions on Power Delivery, 1999, 14(2):567-575.
ZHU Kuanjun, LIU Bin. Calculation of torsional stiffness of bundle conductors in overhead transmission lines[J]. Power System Technology, 2010, 34(3):210-214.
WANG Shaohua, JIANG Xingliang, SUN Caixin. Characteristics of icing conductor galloping and induced dynamic tensile force of the conductor[J].Transactions of China Electrotechnical Society,2010,25(1):159-166.